Z-Series

 up to 1200 kVA

CleanSource® UPS Z-Series systems are designed for maximum flexibility and scalability to support data center applications of all sizes and configurations.  Includes full paralleling support for larger applications.

Active Power multi-module systems are designed to provide modular and expandable UPS power to data center loads.  Start with one flywheel and add additional capacity as load increases.  N+1 flywheel redundancy and dual input support available for maximum reliability.

For access to full guide specifications and product manuals, please contact us.

PowerHouse 400V Specs Contact Us

CleanSource Specifications

Z-Series

Product Specifications

UPS 300Z UPS 600Z UPS 900Z UPS 1200Z
RATING
Maximum kVA 300 600 900 1200
Maximum kW 240 480 720 960
 
INPUT
Voltage1 480 VAC 3-phase, 3-wire plus ground (4-wire optional)
Voltage Range +10% / -15% (programmable)
Frequency 60 Hz +/- 10% maximum (programmable)
+/- 3% (default)
Power Factor 0.99 at rated load and nominal voltage
Harmonic Current Distrotion  
Linear Load <3% at 100% load
Non-Linear Load <8% at 100% load
Current - Nominal (480 VAC) 302 599 898 1,198
Current - Max. Continuous 400 800 1,200 1,600
Current - Max. Non-Continuous 420 840 1,260 1,680
Surge Withstand Meets IEEE 587/ANSI C62.41
Walk-In 1 to 15 seconds (programmable)
 
OUTPUT
Voltage1 480 VAC 3-phase, 3-wire plus ground
Voltage Regulation  
Steady State +/-1% for +/-10% input
Flywheel Mode +/-1% steady state
Transient +/-1% within 50 mSec for 100% load step
Voltage Distortion2 <3% linear loads and
<5% for 100% non-linear loads
Frequency 60 Hz +/- 10% maximum (programmable)
+/- 3% (default)
Slew Rate Adjustable from 0.2Hz/second
to 3.0Hz/second
Current - Nominal (480 VAC) 361 723 1,084 1,445
Overload Capability-Mains Operation
Continuous 10 Min 2 Min 30 Sec 10 mSec
Up to 105% 125% 150% 200% >200%
UPS Efficiency4 97% 98%
 
ENVIRONMENTAL
Audible Noise <72 dBA at 1 meter <75 dBA at 1 meter
Temperature  
Operating 32 to 104° F (0 to 40° C)
Storage -13 to 158° F (-25 to 70° C)
Humidity 5% to 95% (non-condensing)
Altitude3 Up to 3,000 feet (914 meter)
Emissions and Immunity FCC Class A, Subpart J of Part
15/ EN 62040-2
Heat Rejection - Online5  
kW 8.7 12.3 18.4 24.6
BTU/Hr 29,612 41,983 62,975 83,967
 
PHYSICAL DATA
Height 96.0 in
2,438 mm
96.0 in
2,438 mm
96.0 in
2,438 mm
96.0 in
2,438 mm
Width 127.0 in
3,226 mm
170.0 in
4,318 mm
213.0 in
5,410 mm
256.0 in
6,502 mm
Depth 34.0 in
865 mm
34.0 in
865 mm
34.0 in
865 mm
34.0 in
865 mm
Weight 6,375 lbs
2,892 kg
10,875 lbs
4,933 kg
15,750 lbs
7,144 kg
20,250 lbs
9,185 kg
Cable Entry Top or Bottom
 
SAFETY UL 1778 Listed, CUL CAN/CSA 22.2 No. 107.1 Listed
 
(1) Load protected by uninterruptible power supply and generator
(2) Load supported by generator; 10 second break (programmable), sized for mechanical loads
(3) EN 62040-3
(4) DC energy storage off-line
(5) Engine pre-heater off-line
Top of Page
Z-Series
Service Hotline :1.512.744.9290     Corporate HQ: 1.512.836.6464
Corporate HQ: Active Power, Inc
  • 2128 W Braker Ln BK12
  • Austin | Texas | United States | 78758
  • Tel: 1.512.836.6464
  • Fax: 512.836.4511
UK | Active Power Solutions Ltd.
  • Unit 7, Lauriston Business Park
  • Pitchill
  • Evesham | Worcestershire | WR118SN | United Kingdom
  • Tel: 44.1386.870.006
Germany | Active Power (Germany) GmbH
  • An der Leege 22
  • 37520 Osterode am Harz
  • Osterode  |  Germany
  • Tel: 49.0. 5522.507700
China | Active Power (Beijing) Co. Ltd.
  • Rm 510, Tower A, COFCO Plaza
  • 8 Jianguomen Nei Ave
  • Beijing  |  China  | 100005
  • Tel: 86.10.6528.3700
  • Login
  • Contact