The new Active Power CSHD UPS system provides 750 kVA of always-on power protection in the most compact footprint in its kVA class. Competitively priced out-of-the-box, the new CSHD UPS operates at up to 97% efficiency and delivers 30% annual OPEX savings. Parallel up to seven systems for multi-megawatt configurations.

 

For access to full guide specifications and product manuals, please contact us.

PowerHouse 400V Specs Contact Us

HD Specifications

CSHD750 UPS

Product Specifications

CSHD UPS
RATING
Maximum kVA 750
Maximum kW 675
 
INPUT
Voltage1 480 VAC 3-phase, 3-wire plus ground (4-wire optional)
Voltage Range +10% / -15% (programmable)
Frequency 60 Hz +/- 10% maximum (programmable)
+/- 3% (default)
Power Factor 0.99 at rated load and nominal voltage
Harmonic Current Distrotion  
Linear Load <3% at 100% load
Non-Linear Load <4% at 100% load
Current - Nominal (480 VAC) 846
Current - Maximum 1050
Surge Withstand Meets IEEE 587/ANSI C62.41 (planned)
Walk-In 1 to 15 seconds (programmable)
 
OUTPUT
Voltage1 480 VAC 3-phase, 3-wire plus ground
Voltage Regulation  
Steady State +/-1% for +/-10% input
Flywheel Mode +/-1% steady state
Transient +/-1% within 50 mSec for 100% load step
Voltage Distortion2 <3% linear loads and
<5% for 100% non-linear loads
Frequency 60 Hz +/- 10% maximum (programmable)
+/- 3% (default)
Slew Rate Adjustable from 0.2Hz/second
to 3.0Hz/second
Current - Nominal (480 VAC) 903
Overload Capability-Mains Operation
10 Min 10 Sec Immediate
110% 150% 200%
UPS Efficiency3 97%
 
ENVIRONMENTAL
Audible Noise <83 dBA at 1 meter
Temperature  
Operating 32 to 104° F (0 to 40° C)
Storage -13 to 158° F (-25 to 70° C)
Humidity 5% to 95% (non-condensing)
Altitude4 Up to 3,000 feet (914 meter)
Emissions and Immunity FCC Class A, Subpart J of Part
15/ EN 62040-2 (planned)
Heat Rejection - Online5  
kW 20.43
BTU/Hr 69,766
 
PHYSICAL DATA
Height 80.0 in
2,032 mm
Width 132.0 in
3,353 mm
Depth 39.3 in
988 mm
Weight 9,500 lbs
4,309 kg
Cable Entry Top or Bottom
 
SAFETY UL 1778 Listed, CUL CAN/CSA 22.2 No. 107.1 Listed (planned)
 
(1) Optional 4-wire
(2) EN 62040-3
(3) DC energy storage off-line
(4) Derate operating temperature for higher elevations
(5) DC energy storage on-line
Top of Page
CSHD750 UPS
Service Hotline :1.512.744.9290     Corporate HQ: 1.512.836.6464
Corporate HQ: Active Power, Inc
  • 2128 W Braker Ln BK12
  • Austin | Texas | United States | 78758
  • Tel: 1.512.836.6464
  • Fax: 512.836.4511
UK | Active Power Solutions Ltd.
  • Unit 7, Lauriston Business Park
  • Pitchill
  • Evesham | Worcestershire | WR118SN | United Kingdom
  • Tel: 44.1386.870.006
Germany | Active Power (Germany) GmbH
  • An der Leege 22
  • 37520 Osterode am Harz
  • Osterode  |  Germany
  • Tel: 49.0. 5522.507700
China | Active Power (Beijing) Co. Ltd.
  • Rm 510, Tower A, COFCO Plaza
  • 8 Jianguomen Nei Ave
  • Beijing  |  China  | 100005
  • Tel: 86.10.6528.3700
  • Login
  • Contact