RATING
Maximum kVA 625
Maximum kW 625
 
INPUT
Voltage1 380/400/415 VAC 3-phase, 4-wire plus ground
Voltage Range +/- 10% at 380 VAC
Frequency 50Hz (mains synchronised)
(normal operation +/- 0.2% free running)
Power Factor 0.99 at rated load and nominal voltage
Harmonic Current Distortion  
Linear Load <3% at 100% load
Non-Linear Load <8% at 100% load
Current - Nominal (380 VAC) 990
Current - Nominal (400 VAC) 940
Current - Nominal (415 VAC) 906
Current - Maximum 1200
Surge Withstand Meets IEEE 587/ANSI C62.41 (planned)
Walk-In 1 to 15 seconds (programmable)
 
OUTPUT
Voltage1 380/400/415 VAC 3-phase, 4-wire plus ground
Voltage Regulation  
Steady State +/-1% for +/-10% input
Flywheel Mode +/-1% steady state
Transient +/-1% within 50 mSec for 100% load step
Voltage Distortion2 <3% linear loads and
<5% for 100% non-linear loads
Frequency 50Hz (mains synchronised)
(normal operation +/- 0.2% free running)
Slew Rate Adjustable from 0.2Hz/second
to 3.0Hz/second
Current - Nominal (380 VAC) 951
Current - Nominal (400 VAC) 903
Current - Nominal (415 VAC) 871
Overload Capability-Mains Operation
10 Min 30 Sec 10 Sec
110% 125% >150%
UPS Efficiency3 97%
 
ENVIRONMENTAL
Audible Noise <83 dBA at 1 meter
Temperature  
Operating 32 to 104° F (0 to 40° C)
Storage -13 to 158° F (-25 to 70° C)
Humidity 5% to 95% (non-condensing)
Altitude4 Up to 1,000 metre
Emissions and Immunity EN 62040-2 (planned)
Heat Rejection - Online5  
kW 19.15
BTU/Hr 65,388
 
PHYSICAL DATA
Height 80.0 in
2,032 mm
Width 132.0 in
3,353 mm
Depth 39.3 in
998 mm
Weight 9,500 lbs
4,309 kg
Cable Entry Top or Bottom
 
SAFETY UL 1778 Listed (planned), CUL CAN/CSA 22.2 No. 107.1 Listed (planned)
 
(1) 60Hz available
(2) EN 62040-3
(3) DC energy storage off-line
(4) Derating operating temperature for higher elevations
(5) DC energy storage on-line
Top of Page
CSHD625 UPS
Service Hotline :1.512.744.9290     Corporate HQ: 1.512.836.6464
Corporate HQ: Active Power, Inc
  • 2128 W Braker Ln BK12
  • Austin | Texas | United States | 78758
  • Tel: 1.512.836.6464
  • Fax: 512.836.4511
UK | Active Power Solutions Ltd.
  • Unit 7, Lauriston Business Park
  • Pitchill
  • Evesham | Worcestershire | WR118SN | United Kingdom
  • Tel: 44.1386.870.006
Germany | Active Power (Germany) GmbH
  • An der Leege 22
  • 37520 Osterode am Harz
  • Osterode  |  Germany
  • Tel: 49.0. 5522.507700
China | Active Power (Beijing) Co. Ltd.
  • Rm 510, Tower A, COFCO Plaza
  • 8 Jianguomen Nei Ave
  • Beijing  |  China  | 100005
  • Tel: 86.10.6528.3700
  • Login
  • Contact