PowerHouse™
Data center construction costs too much, takes too long, and incurs too much risk. Modular infrastructure backed by software intelligence is the key to solving these problems. PowerHouse is a factory-built and tested electrical system designed for low cost, rapid deployment, and superior management capability.
On This Page
Power Solutions
Resource Library
Active Power has a solution that fits your needs, whether your operation needs a single UPS system or multiple megawatts of power protection. Choose the new Active Power CSHD750 UPS for unmatched power density with a large system building block or the classic CleanSource UPS, available in single and multi-module systems. Both UPS systems offer industry-leading energy efficiency, reliability and TCO.
UPS Systems
Resource Library
When you select an Active Power solution, you get more than an efficient, reliable and green critical power system. You get access to the best service and support in the business. Rely on our trained professionals for expert assessment, implementation, maintenance and support during every phase of your critical infrastructure system deployment and operation. Active Power technicians are available 24x7 to answer questions, provide advice, and react to, diagnose, and resolve warnings and alarms on your system.
On This Page
Resource Library
Active Power
Active Power (NASDAQ: ACPW) designs and manufactures ingenious critical backup power systems and continuous infrastructure solutions that work behind the scenes, enabling datacenters and other mission critical operations to remain 'on' 24 hours a day, seven days a week.
Featured Pages
Resource Library
Active Power's Intelligently Efficient, Inherently Reliable and Economically Green uninterruptible power supply (UPS) and infrastructure solutions enable global innovators to survive power glitches and thrive under challenging business conditions. Browse the categories on this page to watch, listen, download, interact and learn more about how Active Power solutions can work for you.
Active Power | UPS Systems | iC SeriesiC Series
up to 1500 kVA
Specifically designed to meet large capacity needs in 400V markets, Active Power's iC-Series provides unmatched modularity, reliability, and flexibility in a UPS. This system uses 250 kVA modules in a redundant configuration to improve reliability. Supports up to 1500 kVA (1350 kW) in a single line-up – Active Power's largest single system.
For access to full guide specifications and product manuals, please contact us.

iC Series
Product Specifications

UPS 250iG UPS 500iG RATING Maximum kVA 250 500 Maximum kW 225 450 INPUT Voltage 380/400/415 VAC 3-phase, 4-wire plus ground
(from grounded wye source)Voltage Range +10% / -15% (programmable)
+/- 10% at 380 VACFrequency1 50 Hz +/- 10% maximum (programmable)
+/- 3% (default)Power Factor 0.99 at rated load and nominal voltage Harmonic Current Distrotion Linear Load <3% at 100% load Non-Linear Load2 <8% at 100% load Current - Nominal (380 VAC) 358 709 Current - Nominal (400 VAC) 340 674 Current - Nominal (415 VAC) 328 650 Current - Max. Continuous 400 800 Current - Max. Non-Continuous 420 840 Surge Withstand Meets IEEE 587/ANSI C62.41 Walk-In 1 to 15 seconds (programmable) OUTPUT Voltage 380/400/415 VAC 3-phase, 4-wire plus ground Voltage Regulation Steady State +/-1% for +/-10% input Flywheel Mode +/-1% steady state Transient +/-1% within 50 mSec for 100% load step Voltage Distortion <3% linear loads and
<5% for 100% non-linear loadsFrequency 50Hz (mains synchronised)
(normal operation +/- 0.2% free running)Slew Rate Adjustable from 0.2Hz/second
to 3.0Hz/secondCurrent - Nominal (380 VAC) 380 761 Current - Nominal (400 VAC) 361 723 Current - Nominal (415 VAC) 348 696 Overload Capability-Mains Operation Continuous 10 Min 2 Min 30 Sec 10 mSec Up to 105% 125% 150% 200% >200% UPS Efficiency4 97% 98% ENVIRONMENTAL Audible Noise <72 dBA at 1 meter Temperature Operating 0 to 40° C Storage -25 to 70° C Humidity 5% to 95% (non-condensing) Altitude3 Up to 1,000 metre Emissions and Immunity EN 62040-2 Maximum Heat Rejection5 kW 5.8 11.7 BTU/Hr 19,946 39,893 PHYSICAL DATA Height
(w/o wireway or DC bus)1,981 mm 1,981 mm Width 3,226 mm 4,318 mm Depth 865 mm 865 mm Weight 3,164 kg 5,205 kg Cable Entry Top or Bottom SAFETY EN62040-1-1 (1) Load protected by uninterruptible power supply and generator (2) Load supported by generator; 10 second break (programmable), sized for mechanical loads (3) EN 62040-3 (4) DC energy storage off-line (5) Engine pre-heater off-line