Your Data Center, Your Way
Whether your data center is a traditional building, a modular configuration, or a series of containers, Active Power has simple, powerful solutions for you. Rely on us for systems ranging from complete, turnkey PowerHouse™ installations to the efficient power protection of CleanSource® UPS.
On This Page
Power Solutions
Resource Library
CleanSource UPS®
Whether your operation needs a single UPS system or multiple megawatts, Active Power has a solution that fits your needs. CleanSource UPS (uninterruptible power supply) systems deliver highly efficient and reliable backup power. Active Power systems are economically green, delivering environmentally friendly solutions to your economic advantage.
On This Page
UPS Systems
Resource Library
When you select an Active Power solution, you get more than an efficient, reliable and green critical power system. You get access to the best service and support in the business. Rely on our trained professionals for expert assessment, implementation, maintenance and support during every phase of your critical infrastructure system deployment and operation. Active Power technicians are available 24x7 to answer questions, provide advice, and react to, diagnose, and resolve warnings and alarms on your system.
On This Page
Resource Library
Active Power
Active Power (NASDAQ: ACPW) designs and manufactures ingenious critical backup power systems and continuous infrastructure solutions that work behind the scenes, enabling datacenters and other mission critical operations to remain 'on' 24 hours a day, seven days a week.
Featured Pages
Resource Library
Active Power's Intelligently Efficient, Inherently Reliable and Economically Green uninterruptible power supply (UPS) and infrastructure solutions enable global innovators to survive power glitches and thrive under challenging business conditions. Browse the categories on this page to watch, listen, download, interact and learn more about how Active Power solutions can work for you.
Active Power | Continuous Power Solutions | PowerHouse 480VPowerHouse 480V
PowerHouse is available in a series of standard systems from 240 kW up to 960 kW of critical power. The solutions are designed for maximum flexibility and scalability to support a wide variety of data center applications, enabling expansion of backup power infrastructure on demand. Systems include full paralleling support for larger applications.
For access to full guide specifications and product manuals, please contact us.

PowerHouse 480V
Product Specifications
240kW 480kW 720kW 960kW RATING No-Break Capacity 1 (kW) 240 480 720 960 Short-Break Capacity 2 (kW) 200 400 600 800 ELECTRICAL INPUT Voltage 480 VAC 3-phase, 3-wire plus Ground from a grounded wye source Voltage Range +10% / -15% (programmable) Frequency 60 Hz +/- 10% maximum (programmable) (normal operation +/- 0.2% free running) Power Factor 0.99 at rated load and nominal voltage Surge Withstand Meets IEEE 587/ANSI C62.41 Generator Walk-In 1 to 15 seconds (programmable) Harmonic Current Distrotion Linear Load <3% at 100% load Non-Linear Load3 <8% at 100% load Current - Nominal (480 VAC) 299 599 898 898 Current - Max. Continuous 400 800 1200 1600 Current - Max. Non-Continuous 420 840 1260 1680 OUTPUT Voltage 480 VAC 3-phase, 3-wire plus Ground (4-wire with optional 4-wire input) Voltage Regulation Steady State +/-1% for +/-10% input Flywheel Mode +/-1% steady state Transient +/-1% within 50 mSec for 100% load step Voltage Distortion3 Frequency 60Hz (mains synchronised) (normal operation +/- 0.2% free running) Slew Rate Adjustable from 0.2Hz/second to 3.0Hz/second Current - Nominal (480 VAC) No-break/Short-break 361 / 300 723 / 600 1084 / 1000 1445 / 1200 Short Circuit Capacity 65 kAIC Critical Power Efficiency 4 5 98% GENERATOR Generator Size 500kW 1,000kW 1,500kW 2,000kW Tank Capacity (Gallons) 900 1800 2700 3550 Autonomy @ 75% load (hours) 24 24 24 24 EPA Emissions Tier 2 2 2 2 ENVIRONMENTAL Audible Noise 72dB(A) @ 27ft Protection NEMA 2 / IP 12 Temperature Operating 14 to 104 degrees Fahrenheit Storage -13 to 158 degrees Fahrenheit Humidity Up to 99% (non-condensing) Altitude6 Up to 3,000 feet Emissions and Immunity EN 62040-2 PHYSICAL DATA Generator/UPS Container UPS Container Height 11 feet 7 inches 12 feet 1 inch 10 feet 9 inches 10 feet 9 inches Width 10 feet 1 inch 10 feet 1 inch 10 feet 1 inch 10 feet 1 inch Length 43 feet 11 inches 55 feet 10 inches 43 feet 10 inches 46 feet 2 inches Weight 60,000 lbs 97,000 lbs 52,000 lbs 60,000 lbs Cable Entry Side / Bottom Safety EN62040-1-1 Standards UL-2200 (generator), UL-1778 (UPS), UL-1008 (ATS), UL-142 (fuel-tank) (1) Load protected by uninterruptible power supply and generator (2) Load supported by generator; 10 second break (programmable), sized for mechanical loads (3) EN 62040-3 (4) DC energy storage off-line (5) Engine pre-heater off-line (6) Please contact Active Power for higher elevations
PowerHouse 480V
Global Service