PowerHouse 400V

PowerHouse is available in a series of standard systems from 200 kW up to 800 kW of critical power. The solutions are designed for maximum flexibility and scalability to support a wide variety of data center applications, enabling expansion of backup power infrastructure on demand. Systems include full paralleling support for larger applications.

For access to full guide specifications and product manuals, please contact us.

PowerHouse 400V Specs Contact Us

PH Hollywood Squares

PowerHouse 400V

Product Specifications

  200kW 400kW 600kW 800kW
RATING
No-Break Capacity 1 (kW) 200 400 600 800
Short-Break Capacity 2 (kW) 133 266 360 480
 
ELECTRICAL
INPUT
Voltage 380/400/415 VAC 3-phase, 4-wire plus Ground
Voltage Range +10% / -15% (programmable) +10% 380VAC
Frequency 50 Hz +/- 10% maximum (programmable) +/- 3% (default)
Power Factor 0.99 at rated load and nominal voltage
Surge Withstand Meets IEEE 587/ANSI C62.41
Generator Walk-In 1 to 15 seconds (programmable)
Harmonic Current Distortion
Linear Load <3% at 100% load
Non-Linear Load3 <5% at 100% load
Current - Nominal (400 VAC) 400 800 1200 1600
Current - Max. Continuous 520 1040 1560 2000
Current - Max. Non-Continuous 540 1080 1620 2080
OUTPUT
Voltage 380/400/415 VAC 3-phase, 4-wire plus Ground
Voltage Regulation
Steady State +/-1% for +/-10% input
Flywheel Mode +/-1% steady state
Transient +/-1% within 50 mSec for 100% load step
Voltage Distortion3
Frequency 50Hz (mains synchronised) (normal operation +/- 0.2% free running)
Slew Rate Adjustable from 0.2Hz/second to 3.0Hz/second
Current - Nominal (480 VAC) No-break/Short-break 361 / 300 723 / 600 1084 / 1000 1445 / 1200
Short Circuit Capacity 10 x input (mains connected)
Critical Power Efficiency 4 5 98%
 
GENERATOR
Generator Size 350kW 630kW 800kW 1,000kW
Tank Capacity (litres) 470 1000 1500 1500
Autonomy @ 75% load (hours) 8 7 7 6
EPA Emissions Tier 2 2 2 2
 
ENVIRONMENTAL
Audible Noise 72dB(A) @ 8 meter) /  85dB(A) @ 1 Meter
Protection NEMA 2 / IP 12
Temperature
Operating -10 to 40 degrees Celsius
Storage -25 to 70 degrees Celsius
Humidity Up to 99% (non-condensing)
Altitude6 Up to 1,000 meters
Emissions and Immunity EN 62040-2
 
PHYSICAL DATA
Generator/UPS Container
Height 2,896 mm 2,896 mm 3,200 mm 2,896 mm
Width 2,438 mm 2,438 mm 3,353 mm 3,353 mm
Length 12,192 mm 12,192 mm 12,192 mm 12,192 mm
Weight 16,411 kg 22,000 kg 26,000 kg 13,933 kg
Cable Entry Side / Bottom
 
Safety EN62040-1-1
 
Standards UL-2200 (generator), UL-1778 (UPS), UL-1008 (ATS), UL-142 (fuel-tank)
 
(1) Load protected by uninterruptible power supply and generator
(2) Load supported by generator; 10 second break (programmable), sized for mechanical loads
(3) EN 62040-3
(4) DC energy storage off-line
(5) Engine pre-heater off-line
(6) Please contact Active Power for higher elevations
Top of Page
PowerHouse 400V
Global Service : US 1.800.288.5081  International +1.512.744.9290
Corporate HQ: Active Power, Inc
  • 2128 W Braker Ln BK12
  • Austin | Texas | United States | 78758
  • Tel: 1.512.836.6464
  • Fax: 512.836.4511
UK | Active Power Solutions Ltd.
  • Unit 7, Lauriston Business Park
  • Pitchill
  • Evesham | Worcestershire | WR118SN | United Kingdom
  • Tel: 44.1386.870.006
Germany | Active Power (Germany) GmbH
  • An der Leege 22
  • 37520 Osterode am Harz
  • Osterode  |  Germany
  • Tel: 49.0. 5522.507700
China | Active Power (Beijing) Co. Ltd.
  • Rm 510, Tower A, COFCO Plaza
  • 8 Jianguomen Nei Ave
  • Beijing  |  China  | 100005
  • Tel: 86.10.6528.3700